LYGUOHAN / Railway OCS Equipment
AC 25kV · 50Hz National High-Tech Enterprise
Luoyang Guohan Railway Equipment Co., Ltd. Luoyang Guohan Railway Equipment Co., Ltd.

Electric Operating Mechanism

Model 电动机构 Standard — Category Operating Mechanism
电动机构 Electric Operating Mechanism
Model
电动机构
Standard
—
Documents & pricing
Type test reports, factory inspection records and quotations are available on request; tender documents are archived by project.
Product DetailsProduct Details电动机构

Product Overview

The electric operating mechanism is used together with overhead contact system (OCS) disconnectors. Driven by an electric motor, it performs local or remote electric opening and closing and supports remote-control operation.

Applied Standards

The design of this product complies with GB/T 32580.2-2026 "Railway Applications - Fixed Installations - High-Voltage AC Switchgear and Instrument Transformers - Part 2: Disconnectors, Earthing Switches and Load Switches", Clause 6.32 (requirements for mechanical drive systems) and Clause 6.35 (specific requirements for motorized operating mechanisms of OCS disconnectors).

Technical Parameters

ParameterTechnical Requirement (GB/T 32580.2-2026, Clause 6.35)
Applicable objectOCS disconnector
Operation modeElectric (local/remote dual mode)
Motor power supplyDC power supply
Maximum instantaneous starting current≤10 A
Surge protective deviceShall be provided in the power supply circuit; lightning impulse discharge current ≥60 kA (8/20μs), residual voltage ≤2.5 kV
Opening/closing operation time≤4 s (closing and opening)
Remote/local transferA remote/local transfer switch shall be provided; in the local position manual operation applies and remote electric operation is disabled
Components inside the enclosureMotor, limit switches, auxiliary contacts, etc. (excluding relays, contactors and circuit breakers); a heating and dehumidifying device may be provided
Limit switch breaking capacityDC breaking capacity ≥10 A; breaks the motor power supply circuit after closing/opening is completed
Earthing terminalThe enclosure shall provide an earthing terminal marked with the protective earth symbol; the secondary earth bar inside shall be installed insulated from the mechanism enclosure
Enclosure materialStainless steel (recommended)
Degree of protectionNot lower than IP55W (GB/T 4208-2017)
Protection requirementsProtection against cold, moisture, heat, dust, condensation and ingress of foreign objects; the door and the enclosure shall have a locking and anti-loosening mechanism; the roof shall prevent water accumulation
Manual crank handleA manual crank handle for opening and closing shall be provided inside the enclosure
Position indicationThe opening signal shall be issued only after 100% of the contact gap distance is reached; the closing signal shall be issued at a position where the rated current and the dynamic and thermal stability current can be carried safely
Drive connectionThe output shaft and the main drive shaft are connected by stepless adjustment; the mechanical connection is firm and reliable
Overload protectionAn overload protection device that reliably cuts off the motor power supply shall be installed in the operating mechanism
Bearing housing structureFully sealed construction without an "oil filling hole"
Drive connecting partsUniversal joint bearing (with dust-proof structure) + self-lubricating bushings; pins made of anti-rust material
Drive linkageFabricated connecting structure meeting the requirements for mechanical strength, rigidity and corrosion resistance
Water accumulation protectionNo water accumulation shall occur on any component or on the enclosure (especially at drive connections and moving parts)

Structural Features

  • DC motor drive with a maximum instantaneous starting current ≤10A and surge protection
  • Opening and closing operation time ≤4s, fast and reliable
  • Remote/local dual mode; electric operation is disabled in the local position, ensuring maintenance safety
  • Fully sealed bearing housing + universal joint transmission, maintenance-free without oiling
  • Stainless steel enclosure with IP55W protection, suitable for tunnels and outdoor environments
  • Manual opening/closing crank handle inside the enclosure for emergency operation during power failure
  • Reliable position indication signals; the opening signal is issued only when 100% of the contact gap distance is reached

Scope of Application

Suitable for electric operation of 27.5kV / 2×27.5kV disconnectors on electrified railway overhead contact systems.

Note: The above values are the requirements specified by GB/T 32580.2-2026. Parameters of specific products such as motor power, operating torque and mechanical endurance class are subject to the product manual and the factory test report, which are available on request.