LYGUOHAN / Railway OCS Equipment
AC 25kV · 50Hz National High-Tech Enterprise
Luoyang Guohan Railway Equipment Co., Ltd. Luoyang Guohan Railway Equipment Co., Ltd.

Daily maintenance of high-voltage disconnectors

Published 2026-10-22 Category Maintenance

Routine maintenance of OCS disconnectors focuses on contact condition, operating mechanism and insulation:

  • Check the contact blades and fixed contacts for burning, oxidation and pitting; clean and apply conductive grease.
  • Measure contact resistance and compare with the initial value; investigate a rise above 20%.
  • Inspect the operating mechanism for smooth travel, and lubricate the transmission parts.
  • Verify the mechanical interlock and auxiliary contacts; confirm the remote indication matches the actual position.
  • Check insulator surfaces for pollution, cracks and flashover traces; clean or replace as required.
  • Confirm the grounding connection and the cabinet sealing are intact.

Recommended cycle: quarterly visual inspection, annual mechanical and electrical test, and immediate inspection after a short-circuit event.